20W Explosion Proof Exit Lighting - Zone 1 Zone 21 - Voltage 100V-277V

This Explosion Proof emergency lighting is designed for Zone 1, Zone 21 hazardous locations as the exit sign, it is available as an AC (100V - 277V) version.

Applications: In harsh and hazardous environments where illuminated exit signs are required.

ATEX: EN IEC 60079-0-2018; EN 60079-7-2015; EN 60079-18-2015; EN 60079-31-2014;
IECEx: IEC 60079-0-2017; IEC 60079-7-2015; IEC 60079-18-2014; IEC 60079-31-2013;

IECEx & ATEX :

  • “CAUTION-USEFASTENER WITH YIELD STRESS ≥ 640 MPa”;
  • “WARNING – DO NOT OPEN WHEN ENERGIZED”;
  • “WARNING – DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT”;
  • “WARNING – ONLY USE CABLES SUITABLE FOR 85°C”;
  • " WARNING - DETAILED TEMPERATURE CLASS - SEE INSTRUCTIONS”;
  • “THE FLAMPROOF JOINTS ARE NOT INTENDED TO BE REPAIRED”;
  • End user shall use certified cable gland or conduit with suitable type of protection for final installation purpose;
  • External earthing wire shall be connected when used and the cross-sectional areashall be more than 4mm2 or 10AWG;
  • Under rating condition, maximum temperature on the luminaire’s shell shall not be higher than 130℃ for T4.Temperature at cable inlet shall not be higher than allowable limit of the cable applied, to ensure the cable operation normally. The branch point is 83.6℃ and cable entry point is 69.4℃.

 

Features

  • Industry-leading efficacy: up to 120lm/W±5
  • -40°C to +45°C /50°C /55°CAmbient operating temperature
  • Wide optics for uniform illumination
  • 5 years warranty
  • Entry Size: M25Χ1.5 or NPT 3/4”-14
  • Material : Aluminum alloy (ADC12 ) + PC

Parameters

  • Power: 20W
  • Voltage: AC100-277V, 50/60Hz
  •  Power factor: 0.97
  •  Lumen flux: 2400LM
  •  CCT: 2700K - 6500K (Optional)
  •  LEDs: 3030 (6V)
  •  LED Driver: High efficiency driver
  •  Dimension: 329 mm x 125mm x 88.7 mm
  •  Weight: 2.5KG (1 Foot)

Certificate & Standard

Have certified CES-EX-LN-02P fixtures with the IECEX and ATEX standards for hazardous location and environments.

ATEX:
  • II 2G Ex eb mb IIC T5…T6 Gb
  • II 2D Ex tb IIIC T**°C
  • IP66
  • Certificate No:SEV 21 ATEX 0578 X
IECEx:
  • • Ex eb mb IIC T5…T6 Gb;
    • Ex tb IIIC T**°C;
    • IP66
    • Certificate No:IECEx SEV 21.0038X

 

Amounting

Versatile mounting options:

  • Wall Ceiling mounting

 

Send Your Iquiry